D9412GV2/D7412GV2 | Operation and Installation Guide | 12.0 SDI Devices
.
Bosch Security Systems, Inc. | 7/09 | F01U003641-04 65
12.6.3 Address Settings
The DX4020 has specific DIP switch settings for SDI
Address 88 when using the DX4020 for Remote
Programming Software (RPS) or enhanced
communications in a local-area network (LAN) or
wide-area network (WAN) environment. Refer to
Figure 33 for the correct switch settings.
Figure 33: DX4020 DIP Switch Settings
2
=
3
=
4
R
Y
G
B
1
OPEN
123456
78
1 - DIP Switches
2 - ON position
3 - OFF position
4 - SDI Address 88 switch settings
12.6.4 Supervision
Supervision of the DX4020, D9133DC, and
D9133TTL-E at SDI Address 88 is available through
programming that ensures operation between the
module and the control panel.
If supervised and the module does not respond to
control panel supervision polls, SERVC SDI 88
appears at the keypad. The report to the receiver
includes the address of the troubled module indicating
which module needs service.