GV3 Series v8.11 or Higher Programming to Set Up Central Station Reporting | en 11
Bosch Security Systems, Inc. Quick Reference Guide F01U170805 | 02 | 2011.10
4 Programming to Set Up Central Station Reporting
4.1 Basic Telephone Set Up in RPS
1. Go to PANEL WIDE PARAMETERS→Phone and Phone Parameters.
2. Enter the primary telephone number in the Phone 1 field.
3. If a secondary telephone number is required, enter it in the Phone 2 field.
4. Go to Panel Wide Parameters→Routing→Route Group 1.
5. Enter Phone 1 in the Primary field.
6. If a secondary telephone is required, enter Phone 2 in the Backup field.
4.2 Basic Internet Protocol (IP)
1. Go to PANEL WIDE PARAMETERS→Routing→Route Group 1 Primary.
2. Enter SDI 88 Path 1 (or SDI 92 Path 1).
3. Go to AUXPARM→Enhanced Communications.
4. Select or enter the following values:
4.3 Account Number
In RPS, go to AREA WIDE PARAMETERS and enter the account number (up to 10 digits) in
the Account Number parameter.
NOTICE!
You can program these items using RPS and the steps listed below. You can also use keypad
programming with v8.11 and later (refer to the D9412GV3/D7412GV3 Program Entry Guide (P/
N: F01U170807) or the D7212GV3 Program Entry Guide (P/N: F01U170808).
NOTICE!
Enhanced Communications settings usually follow the recommendations of the Central
Stations’ staff.
If using an ITS-DX4020-G for communication, refer to the ITS-DX4020-G Installation and
Operation Guide (P/N: F01U163066).
Parameter Value
Enable Enhanced Communication YES
Path 1 IP Address IP address of Central Station receiver
Path 1 Port Number Port Number of Central Station receiver
Path 1 Poll Rate (seconds)
1
Poll rate recommended by Central Station
Path 1 ACK Wait Time 13 sec (default setting)
Path 1 Retry Count 5 (default Setting)
1
If the control panel is programmed to send a heartbeat poll to the central station, a rate of 75 sec
maintains the virtual link in most network configurations.
NOTICE!
Area 1 is the only area turned on by default.