15 en FLM-420-O8I2-S
F.01U.032.849 | 2.0 | 2010.11 Bosch Sicherheitssysteme GmbH
Technical specifications
POWER
IN OUT I
PI+ | PI- Power supply output 1 to 4
OUT I PI+ | 4- to PI+ | 1- Reference potential (PI+), switched negative potential output 1 to 4
OUT II PII+ | 8- to PII+ | 5- Reference potential (PI+), switched negative potential output 5 to 8
POWER
IN OUT II
PII+ | PII- Power supply output 5 to 8
LSN input voltage 15 to 33 V DC
Max. current consumption from LSN 5,5 mA
Outputs 8, independent
- Max. switched voltage of outputs 30 V DC
- Max. output current rating 700 mA per output (depending on external power supply)
- External power supply 5 to 30 V DC
Inputs 2, independent
1. Line monitoring with EOL:
- EOL resistor Nominal 3,9 kΩ
- Overall line resistance R
Σ
(R
Σ
=R
L/2
+R
L/2
+R
EOL
)
- In standby: 1500 Ω - 6000 Ω
- Short-circuit: < 800 Ω
- Interruption: > 12000 Ω
2. Contact monitoring:
- Max. current strength (current pulse) 8 mA
Minimum activation time of the inputs IN 1 - 2 3,2 s
Maximum cable length of all inputs and outputs
which are connected to the loop or stub and not
electrically isolated from LSN
500 m in total
Permissible wire diameter
0.6 to 3.3 mm
2
Permissible operating temperature -20 °C to +65 °C
Permissible storage temperature -25 °C to +80 °C
Permissible rel. humidity <96 %, non-condensing
Protection class as per IEC 60529 IP 54
Classes of equipment as per IEC 60950 Class III equipment
Housing material and color ABS+PC-FR, signal white (RAL 9003)
Dimensions (W x H x D) Approx. 140 mm x 200 mm x 48 mm
Description Function