ISW-D8125CW-V2 | Installation and Operation Guide | Operation
.
Bosch Security Systems, Inc. | 8/11 | F01U161691-05 15
The keypad shows the point number status.
Figure 20: RF Point Number Status
1 –RF transmitter signal strength
(refer to Table 3 on page 15)
2 RF transmitter state
(refer to Table 3 on page 15)
Table 3: RF Point Number Status Descriptions
Signal
Strength
Description
? The commercial wireless interface module
did not receive at least 30 transmissions to
determine signal strength.
Bad Relocate the RF transmitter.
OK Good signal strength.
State Description
Normal The RF transmitter is working as expected.
Faulted The RF transmitter is faulted.
Tamper The RF transmitter is tampered.
Missing The RF transmitter is missing.
Low Batt The RF transmitter’s battery is low.
Faulted,
Low Batt
The RF transmitter is faulted and its battery
is low.
Tamper,
Low Batt
The RF transmitter is tampered and its
battery is low.
5. To see all off-normal points, press [2] from the
Diagnostics Menu. The keypad scrolls through all
off-normal points at 2-second intervals.
Press [PREV] or [NEXT] to stop the auto scrolling
and view off-normal points one at a time.
6. Press [ESC] to exit the RF Diagnostics menu.
3.10 Other Programming Functions
3.10.1 Programming the ISW-EN5040-T Repeater
If it is necessary to install an ISW-EN5040-T Repeater
into this system, it must be programmed as an RF
transmitter. Refer to Section 3.9.3 Adding a New RF
Transmitter on page 12.
The repeater only sends Low Battery Reports and
Tamper Reports.
For more information, refer to the instructions supplied
with the EN5040-T Repeater.
3.10.2 Programming the Control Panel for RF
Transmitters
Refer to Table 4 for the information that the
commercial wireless interface module sends to the
control panel.
Table 4: Point Transition Reports
If the RF transmitter
sends:
The control panel receives:
A Faulted condition Shorted condition
A Tamper condition Open condition
A Normal condition Normal condition
A Low Battery condition Low Battery condition
Only D9412G, D7412G, D7212G,
D9412, D7412, D7212, and D9112
Control Panels, Version 6.50 and later,
are able to send RF BATTERY LOW
events. See the D9412G/D7412G
Program Entry Guide (P/N: 47775) for
information on programming RF
BATTERY LOW events. The
D9412GV3/GV2, D7412GV3/GV2, and
D7212GV3/GV2 can use any revision. In
addition, RPS Version 3.6 or later and
9000MAIN Handler Version 1.13 or
higher must be used to enable this event.
Komentarze do niniejszej Instrukcji