52 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
This prompt enables a report to be sent when the control panel or an SDI2 bus power supply
module detects a low or missing battery.
3.7 Printer Parameters
Up to three D9131A Parallel Printer Interface Modules can be connected to a D9412GV4 (one
printer for a D7412GV4 and a D7212GV4) SDI bus. Each printer is identified by an address of
17, 18, or 19. Options are available for Routing Reports and area assignments.
P## Area Assign
Assign an area to the printer programmed in Printer Address.
P## Supervised
Supervise this SDI address. Generate Trouble SDI ## Reports and local trouble annunciation if
a problem occurs with this printer or the SDI bus.
Yes Battery Failure and Restoral Reports are sent to the central station.
Modem Reports: Missing or shorted: BATTERY MISSING
Discharge below 12.1 VDC: BATTERY LOW
No Battery Failure and Restoral Reports are not sent to the central station.
NOTICE!
To comply with NFPA standards and UL 864 requirements for Commercial Fire systems
(D9412GV4 and D7412GV4), program this item as Yes.
Default: 1
Selection: 1 to 32 for D9412GV4
1 to 8 for D7412GV4
1 to 4 for D7212GV4
Default: No
Selection: Yes or No
Yes Only one printer can be installed for this printers SDI address.
No More than one unsupervised printer can be installed using this printers
SDI address and the same address DIP switch setting.
NOTICE!
Unsupervised printers sharing the same address setting print the same text.
NOTICE!
Trouble SDI ## Reports are always reported as Area 1, Account 1 Events regardless of where
the SDI device is assigned.
NOTICE!
When P## Supervised is set to Yes and all Printer Event Groups (such as P## Fire Events, P##
Burglar Event, or P## Usr Chng Evt) are set to No, the control panel does not generate
Trouble SDI ## Reports for the printer if the D9131A becomes disconnected.
NOTICE!
The printer cannot show area numbers greater than Area 8. When printed, Areas 9 and higher
print as 00.