D9412GV4/D7412GV4 v2.00 (and higher) Input Points and
Peripheral Devices (D125B, D129, D130) System Wiring
Diagram
Sw. Aux Pwr
Zone B
Zone A
Pnl Common
Pnl Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
COMMON
VOLTAGE RANGES
Open 3.7 - 5.0 VDC
Normal 2.0 - 3.0 VDC
Short 0.0 - 1.3 VDC
+
-
TELCO
RING
TIP
PHONE LI NE
SEIZE D
27
25
EARTH GROUND
COMMON
RELAY A
RELAY B
RELAY C
S4 GROUND FAULT DETECT
Enabled
Disabled
RED
ON when commun icating
OFF whe n idle
ZONEX IN 1
ZONEX POWER +
ZONEX COMMON
PHONE L INE SEI ZED LED
TIP
RING
TELCO CORD MODEL D161
ZONEX OUT 2
ZONEX IN 2
PROGRAMMABLE
ALARM OUTPUTS
Terminals
SWITCHED AUX
and
6
7
Terminal
8
Operation Monitor LED
Pulses when Normal
Flickers when Ringing
GREEN
D5200/D5360
PROG CONN
Point 8, S3 Option
Closed = 1 k EOL
Normal Operation
Open =AB-12 UL
Bell Box 220 k
Point 3
Point 4
161514
Point 1
Point 2
1211 13
Point 5
Point 6
1817 19
Point 7
Point 8
21
20
22
BATTERY NEGATIVE ONLY
BATTERY POSITIVE ONLY
+ AUX POWER
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do not short
Requires Unswitched Outlet
Do not share with other equipment
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
ZONEX OUT 1
N.F.P.A.
Style 4.0
Signaling
Line
Circuits
Aux Power
Zone B
Zone A
Common
Loop B-
Loop A-
Loop B+
Loop A+
Earth Ground
10
9
5
4
3
8
2
1
7
6
11
12
13
Loop A+
Loop A-
Loop B+
Loop B-
TELCO CORD MODEL D161
GREEN
SDI Connector
SDI2 Connector
31
30
29
28
27
26
25
24
EARTH
COMMON
BATTERY NEGATIVE ONLY
BATTERY POSITIVE ONLY.
RELAY A
RELAY B
RELAY C
+ AUX POWER
CLASS 2 TRANSFORMER
16.5 VAC 40 VA 60 Hz
Model D1640
Internally Fused - Do not short
Requires Unswitched Outlet
Do not share with other equipment
.
S4 GROUND FAULT DETECT
Enabled
Disabled
RED
ON when communicating
OFF when idle
Commercial Protected-Premises Control Panel
System is intended to be checked by a Qualified Technician at least every 3 years.
The types of initiating circuits the control panel has been approved for are A, M, W, SS.
The types of signaling the control panel has been approved for are DAC, OT, NC, RevPol.
VOLTAGE RANGES
Open 3.7 - 5.0 VDC Short 0.0 - 1.3 VDC
Normal 2.0 - 3.0 VDC
SDI
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
ZONEX OUT 1
ZONEX IN 1
NFPA
Style 4.0
Signaling
Line
Circuits
YELLOW - Charging Status
RED - Low Battery - 12.1 VDC
10.2 VDC - Battery Load Shed
This equipment should be installed in accordance with the NFPA 70 (National Electrical Code) and
NFPA 72 (National Fire Alarm Code).
ZONEX POWER +
PHONE LINE SEIZED LED
TIP
RING
POWER SUPPLY REQUIREMENTS
The Power Supply provides a maximum of 1.4 Amps for the Control Panel and all
Accessory Devices. For System Loading, refer to the D9412GV4/D7412GV4 Operation
and Installation Guide (P/N: F01U201527).
(P/N: F01U201527) for Power Requirements relating to Terminals 6 and 7 .
CAUTION:
Refer to the D9412GV4/D7412GV4 Operation and Installation Guide
All external connections except Terminal 5 (battery positive) are inherently power
limited. Requirements for battery standby time might reduce allowable output.
WARNING!
Multi-Battery installation requires
Model D122 or D122L Dual Battery
Harness. Improper installation can
be a fire hazard.
Battery: Replace every 3 to
5 years with one or two Model
D126 or D1218 12 V Lead Acid
Batteries.
PROGRAMMABLE
ALARM OUTPUTS
Terminals
SWITCHED AUX
and
Terminal
8
Operation
Monitor
LED
Pulses when
Normal
Flickers when
Ringing
Point 3
Point 4
1614 15
Point 1
Point 2
1211 13
Point 5
Point 6
18
Point 7
Point 8
21
Minimum system requirements for Classification in accordance with ANSI/SIA CP-01-2007:
UL Listed and Classified control unit Model D9412GV4, D7412GV4, or D7212GV4;
UL Listed and Classified keypad Model D1256, D1257, D1260, D1255, D1255R, or D1255RB;
UL Listed Local Bell
CAUTION:
Avoid damage to Panel.
Do not connect 24 V to terminals.
Maximum charging current 1.4 A
NOT USED
NOT USED
Refer to the D9412GV4/D7412GV4 Approved Applications Compliance Guide
(P/N: F01U201525) for System Wiring Diagram, Issue A and for
compatible smoke detectors. 2-wire Compatible Identifier “A”.
Not suitable for remote station protected premises services where separate transmission circuits
are required for fire, supervisory (when applicable) and trouble signals when using D185.
The D9412GV4 Control Panel is UL Listed For Central Station, Remote Station, Local, Auxiliary,
Proprietary, and Household Fire Alarm, and Central Station, Local, Proprietary,
Police Station Connect, Household Burglar Alarm
and Encrypted Line Security when
communicating via a network.
SDI2
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
22
20
17
19
10
9
8
7
6
5
4
3
2
1
6
7
ZONEX COMMON
23
CAUTION:
Avoid damage to Panel.
Do not connect 24 V to terminals.
Maximum charging current 1.4 A
Figure 3.4: Input Points and Peripheral Devices System Wiring Diagram
Callout - Description
1 - (Optional): For 24 V applications use a UL 1481 Listed regulated, power-limited 24 VDC power supply with a
D130 Relay Module. Refer to the D130 Installation Instructions (P/N: F01U072455) for correct wiring
requirements.
2 - D130 Relay Module
3 - D125B Powered Loop Interface Module
4 - To UL Listed two-wire smoke detectors with a fire rated EOL resistor. Refer to Two-Wire Smoke Detectors
section in the Approved Applications chapter in the D9412GV4/D7412GV4 v2.03 Installation and System Reference
Guide (P/N: F01U265457) for a listing of compatible two-wire smoke detectors.
5 - 1 kΩ EOL resistor (P/N: F01U033966): For typical alarm applications.
6 - D129 Dual Class A Initiation Circuit Module: Provides optional Waterflow Alarm Retard feature. Not suitable
for two-wire smoke detectors.
Notice!
For D129, use zero retard except for waterflow devices.
All external connections except Terminal 5 (battery positive) are power limited.
3.3
14 en | Diagrams Control Panel
2014.04 | 03 | F.01U.291.483 UL Installation Instructions Bosch Security Systems, Inc.