D9412GV2/D7412GV2 Release Notes for Version 7.05
F01U003637-02 Page 2 © 2007 Bosch Security Systems, Inc
Use Remote Programming Software
(RPS) version 5.5 and above with this
software version.
To acquire an update for your D5200
Programmer, call the Bosch Security
Systems, Inc. Handler Update System,
toll-free, at (800) 657-4584. Make a
separate phone call for each handler.
Use an analog telephone line with the
D5200. The D5200 dials only pulses.
Refer to Section 10 Updating Handlers in
the D5200 Programming Manual
(P/N: 74-06176-000-B) for details on
updating handlers.
Refer to Table 3 for the required ROM kit part
number.
Table 3: ROM Kit Part Numbers for Version 7.05
Control Panel Model Part Number
D9412GV2 R20-9412V2-0705
D7412GV2 R20-7412V2-0705
2.0 Corrections and Changes
2.1 Version 7.05
Version 7.04 was skipped during
development and was not released.
The default configuration parameters for Path #
ACK Wait Time and Path # Number of Retries
in Version 7.05 firmware are sufficient to meet UL
864 requirements
Changes reset the User Code Tamper condition
when it is reported to the central station in an
Expanded Test Report.
Changes ensure that the keypad emits a tone
when a point is activated during a Walk Test.
Changes prevent the ALARM SILENCED message
from showing on the keypads when the Silent
Alarm bell timer expires. This corrects the
problem described in the GV2 Series Control Panels
Invisible Points Technical Service Note
(P/N: F01U032203).
When a Route Group is configured with an IP
destination in the primary path and a telephone
number in the backup path, a break in the
Network Link Integrity now annunciates locally.
Refer to Enhanced Communication Trouble on page 6
for more details.
Changes ensure that the D928 primary and
secondary phone line failure LEDs operate only
when the Phone Supervision interval is enabled.
Corrections improve the reliability of the direct
connection communication method between the
control panel and RPS through a D5360.
Corrections prevent a programmed # symbol
from being dialed as a zero (0).
If multiple areas use the same relay for the
A# Perimeter Armed
area-wide relay function,
the relay activates when all areas are perimeter
armed. The relay deactivates when the first area
disarms.
The sensitivity of the Ground Fault feature is
modified to be equivalent with Version 6.90 and
to prevent false reports.
The authority scope problem with the Menu Key
Lock feature, described in the GV2 Series Control
Panels Menu Key Lock Technical Service Note
(P/N: F01U032240B), is corrected.
When a user changes the time and date in the
control panel, the corresponding event now
reports consistently the identification of the user
who made the change.
Event reporting for a relay that is set or reset using
the RPS Diagnostics screen is changed to indicate
that the operation was done "By Programmer"
instead of "By Remote.” For example, setting a
relay with RPS now sends a Relay Set by
Programmer at SDI 88 event.
Corrections improve the user interface for the
Door Control sub-menu (CMD 46) in the D1260
and D1260B Keypads.
Changes now require users to have an
L# Door
Control
authority level to enter the Door Control
menu. Formerly, only the
L# Cycle Door
authority was required.
Corrections to the Door Control menu
(COMMAND 46) for the D1260 and D1260B
Keypads restrict the menu items based on the
L# Cycle Door
,
L# Unlock Door
and
L# Secure Door
settings.