Bosch Alarm Panel Interface Manual
Revision 1.4
4.2 Setting the Alarm Options
Workstat0ion alarm options determine how the Workstation behaves when Alarm Events occur for
acknowledgeable alarms. An acknowledgeable alarm is defined as ‘a detected event that meets the criteria
(device programming) to trigger an SG Alarm Event’.
Acknowledgeable alarms may or may not generate an SG
Alarm Event depending on the condition and also on local workstation option settings.
Part 3: Pick the Alarm Options tab and set/verify that the following options are set as needed: the table
below is an abbreviated list of the pertinent workstation alarm options. The remaining alarm options are
discussed in full in the main SG7 Software Manual - Chapter 15.
Click APPLY to save changes
Option Description
Pop up on Alarm (default to checked/on) When checked, System Galaxy pops the SG Alarm Event screen to
the front when an acknowledgeable event is detected.
Automatically call
up DVR Video
(default to checked/on) – allows DVR Viewer to start when alarm event occurs.
When checked, System Galaxy starts the GCS DVR Viewer window if a dvr/camera is
linked to the alarm point. The DVR Viewer shows live video for the camera that is linked to
the activated alarm panel point.
Prevent Appl.
Shutdown w/
Pending Alarms
(default to checked/on) When checked, operator is unable to close the System Galaxy
when a “pending” (unacknowledged) alarm is active in SG Alarm Event screen.
Allow
Acknowledge all
alarms
(default to checked/on) – acknowledge all command clears the alarm events.
When checked, the operator can select the ‘acknowledge all’ option from the command
menu (shortcut menu) in the SG Alarm Event screen.
Acknowledge
alarm priority
range
(Defaults to 0 -9999) - allows client to set the range for acknowledgeable alarm events on a
per workstation basis. (acknowledgeable = alarm point set to ‘ack’)
Acknowledgeable alarms outside of the specified range will not trigger an SG Alarm
Event at the local workstation.
Acknowledgeable alarms inside the range will display on the SG Alarm Event screen for
the local workstation.
Force response
above
(Defaults to 0) - allows client to define the threshold for alarm response based on priority.
(acknowledgeable = alarm point set to ‘ack’)
Acknowledgeable alarms with priorities below this value will not force a response from
the operator.
Acknowledgeable alarms above this value will require a response from the operator
before alarm event will be cleared from the screen.
NOTE: the Alarm Panel Point must be set to require acknowledgement (checked) in the Point Property
screen. Also the
alarm priority set in the Alarm Point Property screen must be within the
acknowledgeable alarm priority range defined in the Workstation/Alarm Options screen.
FIG 4: Workstation Options screen – Alarm Options tab (cropped)