K2200 Series | Installation Guide | 6.0 Configuration and Testing EN | 43
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
Option Switches (For a Slave Controller)
The option switches are fitted at the bottom right of
the circuit board.
For a Slave Controller, the top 3 switches must be
set as shown in Figure 31. Switches 1 to 3 should be
set as in Figure 31.
Figure 31: Slave Controller DIP Switches
1. At the CMD prompt, type in INST and press the
[ENT] button.
CMD INST
2. At PC ADMIN USED, press [N].
PC ADMIN USED N
Press [ENT] to save, press [NXT] to go on.
3. At MASTER DC, press [N].
MASTER DC N
Press [ENT] to save, press [NXT] to go on.
4. Enter the controller address. 2 - 7 (by default, 1 is
the address of the master.
ADDRESS 2
Press [ENT] to save, press [NXT] to go on.
5. Present a key to the faceplate reader. Numbers
will appear. (This should be the same key used
on the Master Controller).
E0 KEY 00000000
Press [ENT] to save, press [NXT] to go on
6. A Password can be set to further protect the
Master Key. Type in the password (8 characters
max).
PASSWORD
Press [ENT] to save, press [NXT] to go on.
7. This is an identity for the master key. i.e.-
MASTER.
ID MASTER
Press [ENT] to save, press [NXT] to go on.
8. This allows the entry of a 12-character name
when adding keys. Press [Y].
ALPHA ID Y
Press [ENT] to save, press [NXT] to go on.
9. At PRINTER TYPE:
Type 0 if you are fitting an Epson or IBM
compatible.
Type 1 if the printer is an OKI Data Microline.
PRINTER TYPE 0
Press [ENT] to save, press [NXT] to go on.
10. At DATE FORMAT:
Type 0 for 'dd-mm-yy' (European style).
Type 1 for 'mm-dd-yy' (US style).
DATE FORMAT 1
END OF SETUP. Press [ESC] to exit back to CMD
Option Switches (For a Master Controller with
Admin Kit and software)
The option switches are fitted at the bottom right of
the circuit board.
For a Master Controller, the top 3 switches must be
set as shown in Figure 32. Switches 1 to 3 should be
set as in Figure 32.
Figure 32: Master Controller (with Admin Kit
and software) DIP Switches
1. At the CMD prompt, type in INST and press the
[ENT] button.
CMD INST
2. At PC ADMIN USED, press [Y].
PC ADMIN USED Y
Press [ENT] to save, press [NXT] to go on.
3. At MASTER DC, press [Y].
MASTER DC Y
END OF SETUP. Press [ESC] to exit back to CMD
prompt. (Nothing else needs to be configured).