K2200 Series | Installation Guide | 6.0 Configuration and Testing EN | 48
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
This value also indicates whether a door contact
is fitted or not. If you set this value to 0 the door
controller will not monitor the door contact.
Press [ENT] to save, press [NXT] to go on.
4. You may use a time profile to automatically open
and close the door. Leave this value at 0 (no
automatic control).
Note:
This requires that the Time Profiles be setup
previous to this step.
DR 1 TP 0
Press [ENT] to save, press [NXT] to go on.
Door 1, Lock Mode (Options)
This display consists of 8 settings represented either
by a number or a - (dash). Each setting is changed by
pressing the number for the option. (See the table
below). When set, the number will appear; when not
set, a - (dash) will replace the number. At start up all
settings will be off.
DR 1 M --------
Press [ENT] to save, press [NXT] to go on.
Table 23: Lock Mode Settings
1 Set: Fail-safe (default). The locks will be
continuously powered, power removed to
unlock the door.
Unset: Fail-secure. Power will be supplied to
unlock the door.
2 See Section 5.4.5 Emergency Override/Free
Exit on page 35.
Set: Door contacts (DR1) produce a Free Exit
report.
Request to Exit (DR2) produces Emergency
Override On when pressed, Emergency
Override Off when released.
Unset: Door contacts operate normally.
Request to Exit operates normally.
3 Set: RTE produces Request for Entry report.
Unset: RTE produces Request to Exit report.
4 Set: AVR reader attached.
Unset: AVR not attached.
5 Set: Readykey Alarm Module/AEM attached.
Unset: No Alarm Module/AEM
6 Exit out of hours. This allows personnel with
access controlled by a time profile to use their
keys outside the time profile if they are leaving
through an exit door.
Set: Exit out of hours allowed.
Unset: Not allowed.
7 Set: Readykey PIN reader with time profiles
attached.
Unset: No Readykey PIN reader with time
profiles
8 This is a special setting that is used in
combination with option 2. Leave this Unset
unless specifically required.
Set: DR1 input will operate the lock output and
generate a Request to Exit transaction.
Unset: DR1 does not operate the lock, if used
as a door contact it will generate a Free Exit
transaction
Lock Mode 2 (Options)
This display consists of a further 8 settings
represented either by a number or a - (dash). Each
setting is changed by pressing the number for the
option. (See the table below). When set, the number
will appear; when not set, a - (dash) will replace the
number. At startup all settings will be off..
DR 1 M2 --------
Press [ENT] to save, press [NXT] to go on.