K2200 Series | Installation Guide | 6.0 Configuration and Testing EN | 45
Bosch Security Systems | 7/03 | 17375 1.3 / 46513C
6.1.7 Setting the Modem Connection
1. From the CMD prompt, type [M] and press
[ENT].
CMD_M
2. Enter to appropriate Baud Rate. Available baud
rate settings are 300, 600, 1200, 2400, 4800,
9600, 19200.
BAUD RATE 1200
Depending on the system type the baud rate
should be:
• Printer attached to faceplate administered
controller (system type 0) : 4800
• Door controller attached to PC interface kit
(system type 1) : 9600
• Door controller attached to Readykey for
Windows (system type 2): 9600
• Door controller attached to Readykey Multi-
Site CNC (system type 2 or system type 3):
the baud rate depends on RS-232 devices
being used, modems, line drivers, etc. 300,
600, 1200, 2400, 4800, 9600, 19200.
Press [ENT] to save, press [NXT] to go on.
3. This setting is important as it will ensure that a
dial-up modem is correctly programmed to auto-
answer. It is also important to ensure that if no
modem is connected, this entry is set to [N].
CONNECT MODEM N
Note:
Applicable only if a dial-up modem is connected to the
controller
N
= There is no dial-up modem connected to the door
controller.
Y
= Enter Y if there is a dial-up modem connected to
this door controller.
Press [ENT] to save, press [NXT] to go on.
4. To select these options, enter the required
numbers (1 to 7) followed by [ENT] to accept the
selection.
SETUP RDPHBTX
For example, entering 1, 2, 5 and 7 selects
those options and displays RD--B-X to show the
options selected. (See Table 21)
Table 21: Setup Options
R When administered by Readykey for Windows only.
This indicates whether Remote Acknowledgement is required for alarms. In this case, if R is showing, a door
alarm will only be cleared at the door controller if it is acknowledged by an operator at the administration system.
This may be the faceplate or a PC. If R is not showing, the alarm will be acknowledged at the door controller
when it is passed to the master controller. This is important if you use the programmable on-board relays
(Readykey for Windows systems only). These relays and those on any attached alarm module will only be reset
when the alarm is accepted by an operator.
D For use with Multi-Site CNC only. Dialback. In the event of an alarm condition or Access Authorized (if set up) the
door controller will dial-back to the Multi-Site CNC using the first number shown in Dialback specification in this
section. If it fails to get through, it will attempt again on the first number. If it fails again, it will try the second
number, if present, twice. This process will be repeated 5 times. If there is still no success it will give up,
generating a Comms Failed transaction
P For use with Multi-Site CNC only. Comms Protection.
This setting activates the Comms protection facility.
See the Protect Comms specification in this section
H For use with Multi-Site CNC only.
Hardware Handshake. Set this if the device being used to communicate with the CNC requires a hardware
handshake (CTS/DTR). The door controller will not send, or stop sending, data when its CTS input is low.
B For use with Multi-Site CNC only.
Auto Baud Rate Select. When a modem obtains a connection, it returns a message stating the baud rate at
which it will communicate. This rate is usually 'negotiated' between modems when a line is established. When
this option is selected, the door controller will adjust its serial baud rate to match the line speed
T Transaction Restriction. Use this setting only when installing the Readykey K2200 Series Controller on a system
such as a Readykey 6000 or Readykey K2000AM, which does not recognize transaction types such as Power
On, Power Off, Auto Relay Set etc .
X Not used.