D7212GV2 | Operation and Installation Guide | 11.0 Arming Devices
48 Bosch Security Systems, Inc. | 2/07 | F01U003805-02
11.3 D279A Independent Zone Control
Any on-board or OctoPOPIT point can be
programmed so that the D279A Independent Zone
Control operates as independent point control (arming
and disarming the point).
Refer to Point Assignments in the D7212GV2 Program
Entry Guide (P/N: F01U003804) for programming
information. Refer to the D279A Operation and
Installation Instructions (P/N: 46458) for wiring and
operation instructions.
11.4 Keyswitch
11.4.1 Description
A maintained or momentary contact arming station
(keyswitch) can be connected to master arm or disarm
any of the areas in the system. The keyswitch is
connected to an on-board or off-board point’s sensor
loop. Relays can be programmed to activate arming
status LEDs for keyswitch arming stations. Refer to
Relays in the D7212GV2 Program Entry Guide
(P/N: F01U003804)
11.4.2 Programming
Refer to Point Assignments in the D7212GV2 Program
Entry Guide (P/N: F01U003804) for the correct
programming for points used for keyswitches.
11.4.3 Installation
For maintained switches, connect the EOL resistor for
the point at the keyswitch so that the switch opens the
circuit when it operates. A short on the circuit produces
an alarm if the area is armed and a trouble if it is
disarmed. Refer to Figure 23.
For momentary keyswitches, connect the EOL resistor
at the keyswitch point so that when the keyswitch
operates, it shorts the resistor. An open on the circuit
causes an alarm if the area is armed and a trouble if it
is disarmed. Refer to Figure 23.
11.4.4 Operation
Maintained Contact
If the point to which the keyswitch is connected is
programmed for a maintained contact, an open on the
arming circuit arms the area. All faulted points are
force armed, regardless of the entry in the FA Bypass
Max program item. Returning the circuit to normal
disarms the area. Refer to Area Parameters and Point
Assignments in the D7212 Program Entry Guide (P/N:
F01U003804)
Momentary Contact
If the point to which the keyswitch is connected is
programmed for a momentary contact, shorting the
arming circuit toggles the area’s arming state between
armed and disarmed. All faulted points are force
armed, regardless of the entry in the FA Bypass Max
program item. Refer to Point Assignments in the
D7212GV2 Program Entry Guide (P/N: F01U003804).
Silencing the Bell
To silence the bell (stop Alarm Bell output) if the
system is armed, position the keyswitch to disarm the
area. If the area is disarmed, turn the keyswitch once to
start the arming process. Turning the keyswitch a
second time stops the arming process and silences the
bell.
Figure 23: Keyswitch Wiring
1
2
3
4
5
3
4
5
6
7
1 - Maintained keyswitch
2 - Momentary keyswitch
3 - Common
4 - Point input
5 - 1 k
Ω
or 33 k
Ω
resistor
6- Open on a circuit arms the area
7 - Short on a circuit toggles the arming state
Use 1 k
Ω
EOL resistors if using one of the zones on the control panel or an OctoPOPIT. Use a 33 k
Ω
resistor if using a POPIT.