Table 138: General System Troubleshooting (continued)
Symptom Probable Cause Possible Solutions
Fire Trouble ____________ zone
number.
Fire zone wiring problems. If you try to disable the zone by
reprogramming it, you need to reset the
control panel by either entering then
exiting programmer's mode, or
removing then restoring power to the
control panel.
Dirty Chamber ____________ zone
number.
A multiplex smoke detector has failed its
internal sensitivity test.
Clean or replace the dirty smoke
detector or chamber.
Do not use water to
clean the chamber.