TECHNICAL SPECIFICATIONS:
SCOPE OF WORK:
The Intent of these specifications is to obtain complete
equipment and services (engineering, coordination, outside
construction, electrical, installation, testing, clean-up,
disposal, supervision, maintenance, monitoring, training,
etc.) required for new integrated and fully functional
Security Systems for Chippens Hill Middle School.
Security systems include Access Control, Intrusion
Detection and CCTV components as well as interfacing with
existing fire alarm panel(s).
Existing Radionics security devices, control panel, door
contacts and motion detectors, are to be left in place and
incorporated into the new system.
Outside construction involves installation of underground
conduits from the school building to existing light poles
located in the upper parking lot.
Installation work shall also provide remote access to the
systems from the Bristol Board of Education Office and the
Bristol Police Department.
Existing construction consists of six (6) building pods to
create the Chippens Hill Middle School. Pods are
interconnected with expansion joints. Vendor is
responsible for providing, as part of the turn-key
installation, compliant cable pathways passing through each
expansion joint. Refer to the security drawings for
locations of the expansion joints.
Przeglądanie stron 0
1 2 3 4 5 6 ... 36 37

Podsumowanie treści

Strona 1

TECHNICAL SPECIFICATIONS: SCOPE OF WORK: The Intent of these specifications is to obtain complete equipment and services (engineering, coordinati

Strona 2

construction with a record of successful in-service performance. D. Product Options: Drawings indicate size, profiles, and dimensional requirements o

Strona 3

2. Interior, Controlled Environment: System components, except central-station control unit, installed in air-conditioned, temperature-controlled

Strona 4

protective covering for storage and identified with labels describing contents. 1. Access Control, Intrusion Detection, and Intercom Devices: F

Strona 5

PART 2 - PRODUCTS 2.1 MANUFACTURERS A. In other Part 2 articles where titles below introduce lists, the following requirements apply for product sele

Strona 6

with requirements in NEC code and as recommended by manufacturer for type of line being protected. C. Interference Protection: Components shall be u

Strona 7

C. Exterior Electronics: NEMA 250, Type 4X fiberglass. D. Corrosion Resistant: NEMA 250, Type 4X PVC. E. Screw Covers: Where enclosures are acces

Strona 8

2.6 ACCESS CONTROL ALARM MONITORING SYSTEM A. ACAM file server shall be Integral Technologies Continuum SE® security management system, with no equi

Strona 9

matrix printer of a minimum of 160 CPS print speed using tractor-feed fan fold paper. Quantity of one (1) is required to be installed at the Security

Strona 10

c. 3-1/2" Diskette Drive d. CD-RW Drive e. Audio sound card and speakers f. Microsoft SQL 2000 Server Software g. Microsof

Strona 11

a. On-line alarm reports and event transactions shall be printed on the on-line event printer. The printer shall be a dot matrix printer utilizin

Strona 12

PART 1 - GENERAL 1.1 The Intent of these specifications is to obtain complete equipment and services (engineering, installation, testing, maintenanc

Strona 13

hardware, provision, installation and operation, to ensure proper operation of all reader doors. 2.7 SYSTEM SOFTWARE A. The security management syst

Strona 14

download database and upload transaction history based on operator commands. s. Variable card formats. t. Software for integrated video imaging/badg

Strona 15

directly from the back up magnetic media without the need to interrupt normal on-line activity of the ACAM system. D. Historical Reports. a. The sys

Strona 16

1) Standard cardholder record reports may be requested by an operator, with the data records sorted numerically by encoded card number, alphabeticall

Strona 17

capability shall include, but is not limited to the following: a. Card number, serial number, employee number or name. b. Card readers. c

Strona 18

necessary interface and/or control cables required for connection to the network. Configuration shall be based on the following: Base Bid: Two (2) D

Strona 19

4mm varifocal length lens with an iris range of f1.6 to 200. The cameras shall be installed in locations as shown on the attached security drawings.

Strona 20

7. Alarm system keypad shall be Ademco 6139 with no equivalent 2.13 AUDIO/VIDEO INTERCOM SYSTEM A. Acceptable Manufacturers: Aiphone Communicatio

Strona 21

1. All conduits to be direct buried shall be 2" schedule 80 PVC if non-encased, or schedule 40 PVC if concrete encased. 2. All conduit

Strona 22

PART 3 - EXECUTION 3.1 EXAMINATION A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for install

Strona 23

Contractor is responsible for coordinating any required programming to ensure access to the new high school security systems. Board of Education requ

Strona 24

spaces and in interior hollow gypsum board partitions. Conceal raceways and wiring except in unfinished spaces and as indicated. Minimum raceway siz

Strona 25

manufacturer. Do not install such items near devices they serve. G. Identify components with engraved, laminated-plastic or metal nameplate for cent

Strona 26

connections, and to assist in field-testing. Report results in writing. C. Perform the following field tests and inspections and prepare reports:

Strona 27

g. Test each initiating and indicating device for alarm operation and proper response at control unit. h. Test both primary and secondary power.

Strona 28

6. Basic troubleshooting guide intended to identify the source of system problems. 7. Overall system configuration and restore procedures. C. E

Strona 29

C. The Contractor must uncover and expose all known conflicts along the trench route to permit gradual conduit deviations and realignments. D. To a

Strona 30

4. A minimum horizontal separation of 12 inches must be maintained between the electrical and telecommunications duct banks. 5. Conduits buried und

Strona 31

poured in lifts greater than three tiers in height. R. All surface areas which are disturbed or damaged during excavation and placement must be rest

Strona 32

2. Audio/Video Intercom with hardwired, modular components to perform monitoring, viewing, voice communication and selective release of door lock m

Strona 33

control and CCTV systems in the Bristol Chippens Hill Middle School. Bristol's city-wide computer network consists of local area networks (LAN&

Strona 34

room. It is required for the successful vendor to integrate, and maintain, the existing Radionics systems with the newly provided and installed syste

Strona 35

installed for remote access to CCTV at all school locations. H. New systems shall be connected to each school’s LAN using CAT 5e wiring. Provide and

Strona 36

type, and size, and type and size of wire and cable fill for each raceway run. 3. UPS: Sizing calculations to provide a minimum of eight (8) hour

Strona 37

E. Operation and Maintenance Data: For access control, intrusion detection, and intercom system(s) to include in emergency, operation, and maintenan