2.6 ACCESS CONTROL ALARM MONITORING SYSTEM
A. ACAM file server shall be Integral Technologies
Continuum SE® security management system, with no
equivalent, complete with CPU, keyboard, 17" LCD
color monitor, all required database management,
configuration software, database storage system
software and hardware, as well as complete
browser based ACAM software package including a
dynamic alarm graphical user interface. The ACAM
system shall also support video badging system
Interface, CCTV subsystem interface, elevator
control, high integrity dial-up, and other
subsystem functions as defined in the
specifications and contract documents. ACAM file
server shall communicate with ACAM workstations
over an industry standard Ethernet local area
network (LAN). Location of ACAM file server shall
be co-located with the security system head-end
and as specified in contract documents and
drawings.
B. ACAM workstation shall be Integrated Technologies
Continuum SE® security management system, with no
equivalent, 17" LCD color monitor and keyboard
for database entry, operator requested reports
and alarm/event reporting. Operator interface
shall be browser-driven through easy to
understand screens with point and click buttons.
ACAM workstation shall communicate with ACAM
server over an industry standard Ethernet LAN.
One (1) workstation shall be located in the
school's Main Office with an exact location
coordinated by the vendor and school official.
C. Dynamic alarm color graphical user interface with
full graphic map/floor plan import and display
capability. The system shall have the capability
to simultaneously display floor plan maps with
coded interactive alarm icons and indications,
together with audible alarm, descriptive alarm
text and operator instructions. Quantity and
location of alarm color graphic maps, alarm
points and active response workstations shall be
as specified in contract documents and drawings.
D. Logging and report printers shall be provided.
Logging printer shall be a black-and-white, dot