D7212GV2 | Program Entry Guide | 6.0 GV2AUX EN | 130
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
Early Ambush Timer
Default: 10 min
Selection: 5 to 30 min
The programmed time is the maximum value of the
Early Ambush Timer. When Early Ambush is set to
Yes for a specified area (refer to A# Early Ambush on
page 45) and the area is disarmed, the user has the
amount of time programmed here to enter a second
code into the keypad.
If a second passcode is not entered within the
programmed time, a Duress event is generated based
on the first user code. Duress reports mush be enabled
in Routing in order to be sent to a central station.
Secondary Ambush Code
Default: Unique
Selection: Unique or any
Unique
The code used to end the timer must
be different from the code used to
disarm the area.
Any
The timer can be stopped using a
different code, or the same code that
disarmed the area.
The Secondary Ambush Code determines whether the
same passcode can be used to begin and end the Early
Ambush process.
Abort Window
Default: 30 sec
Selection:
15 to 45 sec
This parameter determines the amount of time the
control panel delays a Burglar Alarm event from a
point with
P## Alarm Abort
set to Yes. If an alarm
silence operation is performed before this time elapses,
the alarm transmission is aborted and the keypad
shows an optional ALARM NOT SENT message. When
an alarm transmission is successfully aborted, no event
is written to the control panel event log.
When an abort alarm timer starts, it does not stop until
an alarm silence operation is performed or the time
expires.
This feature does not apply to Fire Alarms
or invisible point alarms.
For SIA CP-01 Compliance:
Abort Window
is a required parameter.
To meet UL requirements, the combined
Entry Delay time and Abort Window time
must not exceed 60 sec. For Entry Delay
time programming information, refer to
P## Entry Delay in the Point Responses
section of your control panel’s program
entry guide.
UL note: Maximum settings for residential
use:
Exit Delay – 120 sec
Entry Delay = 45 sec bell
Off-Premise Transmission = 60 sec
Maximum settings for commercial use:
Exit Delay – 120 sec no line security
Entry Delay = 60 sec bell
Off-Premise Transmission = 60 sec
The system must use both the bell and
off-premise transmission.
Passcode Length
Default: 0
Selection:
0, 3, 4, 5, or 6
0 Sets a variable length for user
passcodes, allowing for backward
compatibility.
3, 4, 5,
or 6
Sets a fixed length to all user
passcodes.
During entry delay, the code is accepted when the last
digit is pressed to disarm the area.
For SIA CP-01 Compliance:
Passcode Length
must be set to 3, 4, 5, or 6.