Area
Default: 1
Selection:
1 to 4
Enter the area number you are programming.
• The D7212GV2 allows programming for
Areas 1 through 4 only.
• The D5200 Programmer allows entries
for Areas 5 through 8, but they cannot be
used on the D7212GV2.
• If Areas 5 through 8 are programmed for
the D7212GV2, the keypad displays
CALL FOR SERVICE.
A# Fire Time
Default: 6
Selection:
1 min to 90 min
Enter the number of minutes the bell rings for Fire
Alarm points. The relay activated for this time is
programmed in
A# Fire Bell
in Area Relays.
The bell output begins as soon as the fire alarm occurs.
It shuts off the bell when the programmed number of
minutes expires.
If programmed for 1 min, the output can be anywhere
from 0 to 60 sec of bell time. Program Fire Time for 2
min or more to ensure you have ample output time.
Check with your AHJ to determine the
appropriate bell time for your
geographical area.
A# Fire Pat
Default: Pulse
Selection:
Steady, Pulse, CaStnd, TmCod3
Steady Steady Output
Pulse Pulse March Time
120 beats per min, at an even tempo
CaStnd California Standard
10 sec On + 5 sec Off + 10 sec On + 5
sec Off. This sequence repeats until
bell time expires.
TmCod3 Temporal Code 3
0.5 sec On, 0.5 sec Off, 0.5 sec On, 0.5
sec Off, 0.5 sec On, 1.5 sec Off;
pattern repeats. This sequence repeats
for a minimum of 3 min and with a ±
10% tolerance.
Select the bell pattern this area uses to signal an alarm
on a Fire point.
Press the [Space] bar to scroll through the selections.
Press [Enter] when the correct selection appears in the
display.
When an alarm occurs on two Fire points
sharing the same relay, the bell pattern of
the most recent fire event takes
precedence.