D7212GV2 | Program Entry Guide | 2.0 GV2MAIN EN | 75
Bosch Security Systems, Inc. | 1/08 | F01U003804-04
Summary Fire Tbl
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Activates when any Fire point in the control panel is in
trouble, or if a Fire Supervision point is missing. This
relay provides a steady output until all Fire points
restore to a normal condition.
Summary SupFire
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Activates when any Fire Supervisory point in the
control panel is in a supervisory condition (off-normal).
This relay provides a steady output until all Fire
Supervisory points are restored to a normal condition.
Summary Trouble
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Activates when any Non-fire point in the control panel
is in a trouble condition. This relay provides a steady
output until the user at the keypad acknowledges the
trouble.
Summary SupBurg
Default: Blank
Selection: Blank, 1 to 24, A, B, or C
Activates when any Non-fire Supervisory point in the
control panel is in a supervisory condition, or if a
Supervisory Burg point is missing. This relay provides
a steady output until the user at the keypad
acknowledges the condition.