Item Option
Event Code 4 0 = Reserved
4 1 = Reserved
4 2 = Reserved
4 3 = Reserved
4 4 = Reserved
4 5 = Chime
4 6 = Zone not sealed
4 7 = Zone not sealed after Exit Time
4 8 = Reserved
4 9 = AC MAINS cycle (60 Hz or 50 Hz)
4 10 = Area 1 – zone unsealed
4 11 = Area 2 – zone unsealed
4 12 = Reserved
4 13 = Reserved
4 14 = Reserved
4 15 = Reserved
5 0 = Reserved
5 1 = Reserved
5 2 = Area 1 in alarm
5 3 = Area 2 in alarm
5 4 = Reserved
5 5 = Reserved
5 6 = Area 1 armed
5 7 = Area 2 armed
5 8 = Reserved
5 9 = Reserved
5 10 = Area 1 disarmed
5 11 = Area 2 disarmed
5 12 = Reserved
5 13 = Reserved
5 14 = Any areas armed
5 15 = Any areas disarmed
Event Code
6 0 = Reserved
6 1 = Reserved
6 2 = Remote control 4
6 3 = Remote control 5
6 4 = Remote control 6
6 5 = Remote control 7
6 6 = Remote control 8
6 7 = Remote control 9
6 8 = Remote control 10
6 9 = Remote control 11
6 10 = Remote control 12
Polarity (Modes) 0 = Output not used
1 = Normally open, going low
2 = Normally open, pulsing low
3 = Normally open, one shot low
4 = Normally open, one shot low (reactivate)
5 = Normally open, one shot low (can reset)
6 = Normally open, one shot low (alarm)
7 = Normally open, latching low
8 = Normally low, going open
9 = Normally low, pulsing open
10 = Normally low, one shot open
11 = Normally low, one shot open
(reactivate)
12 = Normally low, one shot open (can
reset)
13 = Normally low, one shot open (alarm)
14 = Normally low, latching open
Time Base 0 = Not Used
1 = 200 ms
2 = 1 sec.
3 = 1 min.
4 = 1 hr.
Time Base Multiplier Enter a value between 00 and 99.
Table 15.2: Output Item Options
* One Shot Mode
When you program the output polarity as one shot, the time base is multiplied by the time
base multiplier. (For example, if the time base = 2 and the multiplier = 05, the output operates
for 5 sec.)
*Pulsing Mode
When you program the output polarity as pulsing, the time base becomes the ON time and the
multiplier becomes the OFF time. The OFF time is the time base x the multiplier. (For
example, if you want the output to pulse 1 sec. ON and 5 sec. OFF, you would program time
base as one and the multiplier as five.)
Control Panel Programmable Outputs | en 131
Installation Guide 2014.07 | 00n | F01U298026
Przeglądanie stron 130
1 2 ... 126 127 128 129 130 131 132 133 134 135 136 ... 151 152

Komentarze do niniejszej Instrukcji

Brak uwag