Codepad Panic Report
A Panic Alarm Report (Contact ID Event Code 120) is sent to the base station receiver when a
user presses either [1] and [3] or [STAY] and [AWAY] at the same time. A Panic Alarm is
audible, but you can program the alarm as silent by selecting Option 1 in Location 493.
Codepad Fire Report
A Fire Alarm Report (Contact ID Event Code 110) is sent to the base station receiver when a
user presses [4] and [6] at the same time. A Fire Alarm is audible, but you can program the
alarm as silent by selecting Option 2 in Location 493. A distinct fire sound is emitted through
the horn speaker to indicate this type of alarm. The fire sound is different than the burglary
sound.
Codepad Medical Report
A Medical Report (Contact ID Event Code 100) is sent to the base station receiver when a user
presses [7] and [9] at the same time. A Medical Alarm is audible, but you can program the
alarm as silent by selecting Option 4 in Location 493.
AUX Power Supply Fail Report
A System Trouble Report (Contact ID Event Code312) is sent when either the codepad AUX
power supply is blown or the AUX power supply malfunctions. The system reports the event
approximately 10 sec after the failure.
AUX Power Supply Fail Restore Report
A System Trouble Restore Report (Contact ID Event Code 312) is sent when the AUX power
supply is reset. The system reports the event approximately 10 sec after power supply is
reset.
AC Fail Report
An AC Fail Report (Contact ID Event Code 301) is sent to the base station receiver when the
AC MAINS supply is disconnected for 2 min. If you do not want an AC Fail Report to be sent
until the AC MAINS supply is disconnected for 1 hour, select Option 1 in Location 494. If you
want to ignore AC Fail, select Option 2 in Location 494.
AC Fail Restore Report
An AC Fail Restore Report is sent when the AC MAINS supply is connected continuously for
longer than 2 min.
Low Battery Report
A Battery Test Failure Report (Contact ID Event Code 302) is sent to the base station receiver
when the system’s battery voltage falls below 11 VDC or when a Dynamic Battery Test detects
a low capacity battery.
The control panel continually monitors the battery voltage. A Dynamic Battery Test is done
every time the system is armed and every 4 hours after the control panel is powered up.
17.12
17.13
17.14
17.15
17.16
17.17
17.18
17.19