To copy the direct link adapter memory to the control panel:
1. Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s
Programming Mode. Two beeps sound and the STAY and AWAY indicators flash on the
remote codepad to indicate you entered Installer’s Programming Mode. The remote
codepad displays the data stored in Location 0000.
2. Connect the direct link adapter to the Bosch SDI2 Bus pins at the bottom of the control
panel printed circuit board.
3. Enter [9 6 3 #]. Two beeps sound after the direct link adapter’s data is successfully
copied to the control panel. A long beep indicates that the direct link adapter is corrupt
and must be erased to clear the corrupt data.
4. Enter [9 6 0 #] to exit from Installer’s Programming Mode. The STAY and AWAY indicators
are extinguished on the remote codepad to indicate the system is disarmed.
5. Remove the direct link adapter from the control panel Failure to exit from Installer’s
Programming Mode before removing the direct link adapter can corrupt the direct link
adapter.
Command 965 - Set up Domestic Dialing Format
Command 965 simplifies the setup of the domestic dialing format to a one-step operation.
To set up domestic dialing format:
1. Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s
Programming Mode. Two beeps sound and the STAY and AWAY indicators flash on the
remote codepad to indicate you entered Installer’s Programming Mode. If on a text
codepad, go to menu 81 Address Program. The remote codepad displays the data Mode.
The remote codepad displays the data stored in Location 0000.
2. Enter [9 6 5 #]. The command automatically sets Receiver 1 to domestic reporting and
sets other locations or Receiver 2 only (refer to the table Command 965 Defaults below).
No other locations are changed when you issue command 965.
3. If on a text codepad, enter the Installer Code (the default is (1234) and press [#] to enter
Installer’s Programming Mode. Go to menu 747 Set Up Domestic Dialing Format, then
save and exit.
The transmission format is automatically set for domestic dialing and the Subscriber ID
Number set for one identification beep. All reports, except Zone Status reporting and System
Status reporting, are allocated to Receiver 1 for domestic dialing.
Zone Status Reports including Zone Bypass, Zone Trouble, Sensor Watch, and Alarm Restore
codes, and System Status Reports including AUX Power Supply Fail, AC Fail, Low Battery, and
Access Denied Reports are allocated to Receiver 2 and do not report unless Receiver 2 is also
set up to report.
Location
Description Default Value Setting
033 Transmission Format 4 Domestic
034 and 039 Subscriber ID Number 0, 0, 0, 0, 0, 1 1 Beep
392 Zone Status Reporting Options 2 Receiver 2 only
403 Arm/Disarm Reporting Options 2 Receiver 2 only
424 System Status – Access Denied 6 Access Denied
427 System Status Reporting Options 2 Receiver 2 only