When you select a 24-Hour Fire Zone to be isolated, a Contact ID Event Code 571 is sent. If
you select another 24-Hour Zone to be isolated, a Contact ID Event Code 572 is sent.
Standard isolating
Standard isolating allows any operator to isolate zones because no code is required.
1. Press [STAY] twice.
Three beeps sound and the STAY indicator flashes.
2. Enter the number of the zone to be isolated and press [STAY].
The indicator for the zone flashes.
24-Hour zones are automatically isolated as soon as you press [STAY]. All other Burglary Zones
are automatically isolated only after the system is armed.
3. Repeat Step2for each zone you want to isolate.
Notice!
As each zone is selected to be isolated, the corresponding zone indicator flashes. If you make
a mistake, enter the incorrect zone number and press [STAY]. This zone is no longer selected
to be isolated and the zone indicator is extinguished.
4. Press [AWAY].
Two beeps sound and the system returns to the disarmed state.
The indicators for the selected zones continue to flash until the next time the system is
disarmed.
Example:
To manually isolate zones 1, 3, and 4, press: [STAY][STAY][1][STAY][3][STAY][4][STAY]
[AWAY]
Code to isolate
The code to isolate method permits only those User Code holders with a priority level that
includes Code to Isolate. The standard isolating method is disabled for any User Code with
this priority level set.
1. Press [STAY].
2. Enter your code and press [STAY].
Three beeps sound and the STAY indicator flashes.
If you attempt to enter isolating mode with a User Code that is not set for Code to Isolate, the
system ignores the attempt.
3. Enter the number of the zone to be isolated and press [STAY].
The indicator for the zone flashes.
24-Hour zones are automatically isolated as soon you press [STAY]. All other Burglary zones
are automatically isolated only after the system is armed.
4. Repeat Step3for each zone you want to isolate.
Notice!
As each zone is selected to be isolated, the corresponding zone indicator flashes. If you make
a mistake, enter the incorrect
zone number and press [STAY]. This zone is no longer selected to be isolated and the zone
indicator is extinguished.
5. Press [AWAY].
6.12
6.13
Control Panel System Operations | en 57