8-46 Drive Functions MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Note: This change bit is cleared again by reading S-0-0012, Class 2
diagnostics. Using parameter S-0-0097, Mask class 2
diagnostic warnings can be adjusted in terms of their effect
on the change bit.
Note: To reactivate the drive, the E-Stop input must be deactivated
and another positive edge must be applied to the external
drive enable.
If the interpretation was set as an error in P-0-0008 (bit 2 = 0), the
reaction selected in bit 1 is carried out:
The diagnostic error message F4034 Emergency-Stop (or F6034
Emergency-Stop) appears.
Bit 15 is set in parameter S-0-0011, Class 1 diagnostics.
Bit 13 (drive interlock, error in class 1 diagnostics) is set in the drive
status word of the drive telegram. The error message can be cleared
via command S-0-0099, C0500 Reset class 1 diagnostics or the
"Esc" button of the control panel if the E-Stop input is no longer active.
Note: The error reaction is carried out without delay, independent of
parameter P-0-0117, Activation of NC reaction on error.
If bit 1 = 0 was set in parameter P-0-0008, the drive is shut down
according to the error reaction parameterized via P-0-0119, Best
possible deceleration.
The diagnostic message upon activating the E-Stop input then reads
F4034 Emergency-Stop.
If bit 1 = 1 was set in parameter P-0-0008, the drive, when the E-Stop
triggers, is braked with maximum torque to speed = 0, independent of the
error reaction defined in parameter P-0-0119. This setting corresponds to
the best possible deceleration "velocity command value reset".
The diagnostic message upon activating the E-Stop input then reads
F6034 Emergency-Stop.
Notes on Commissioning
Activation and Polarity of the E-Stop Input
Prerequisite for using the function is the assignment of bit 0 of parameter
P-0-0223 to a digital input (see "Digital Inputs/Outputs: Notes on
Commissioning" in chapter "Extended Drive Functions"). A voltage level
at the digital input therefore also affects bit 0 of P-0-0223.
Note: Without this assignment to the digital input the E-Stop reaction
fails to occur in spite of the input having been activated!
The activation of the E-Stop input and the selection of a reaction for
shutdown of the drive is carried out via bit 0 of parameter P-0-0008,
Activation E-Stop function (see also Parameter Description P-0-0008).
P-0-0008, bit 0 (activation E-Stop):
bit 0 = 0 function not activated
bit 0 = 1 function activated
E-Stop Reaction
P-0-0008, Bit 1
Assigning Digital Input
Activating E-Stop