DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 114
Bosch Security Systems | 8/04 | 4998153891C
Table 25: Output Function Types (continued)
Digit 1 Digit 2 Function Type Description
1 7 Silent Alarm Activated by alarm on non-fire zones programmed for No Alarm Output.
Follows Bell Time for Steady and Pulse modes. PIN stops. The following
conditions activate Silent Alarm:
- ABC Key programmed for Fire or Emergency and no Alarm Output
- RF Keyfob programmed for Fire or Emergency and no Alarm Output
- A zone programmed for Fire or Fire with Verify and no Alarm Output
- Any zone not programmed for Invisible Panic that is programmed for no
Alarm Output
- Any armed zone programmed as a controlled type that goes from
Supervised to Missing and programmed for no Alarm Output
- Any armed keyswitch programmed for no Alarm Output that goes from
Supervised to Missing or Short to Missing
- Any zone programmed for Swinger Count and Swinger Count for Alarm
Output that reaches its programmed value
1 8 Alarm – All On, Perimeter Only,
and Partial On Arming, Non-fire
24 hour alarms
Activated by alarm on zone when All On, Perimeter Only, and Partial On
Armed, or by alarm on Non-fire 24 hour zone, and by user/installer ‘Bell
Test’. Follows Bell Time for Steady and Pulse modes. PIN resets. Follows
programming for ‘Alarm’ output types.
1 9 Alarm – Perimeter Only and
Partial On Arming Modes, Non-
fire 24 hour alarms
Activated by alarm on zone when Perimeter Only, and Partial On Armed,
or by alarm on Non-fire 24 hour zone, and by user/installer ‘Bell Test’.
Follows bell time for Steady and Pulse modes. PIN resets.
Follows programming ‘Alarm’ output types.
1 10 Alarm –Controlled zones, 24-hr
zones (Fire and Non-Fire)
Activated by alarm on zone when All On, Perimeter Only, and Partial On
Armed, or by alarm on Fire and Non-fire 24 hour zone, and by
user/installer ‘Bell Test’. Follows bell time for Steady and Pulse modes.
Pulses in Temporal Code 3 format for Fire alarms only. PIN resets.
Off-board outputs cannot provide output in Temporal Code 3 format
(only on-board outputs). Off-board outputs provide a steady output.
Follows programming for ‘Alarm’ output types. Temporal Code 3 for
Fire alarms only.
1 11 Fire Alarm Activated by alarm on Fire zone, and by user/installer ‘Bell Test’. Follows
Bell Time. Pulses in Temporal Code 3 format. Mode and Time parameters
do not apply. PIN resets. Off-board outputs cannot provide output in
Temporal Code 3 format (only on-board outputs). Off-board outputs
provide a steady output. Follows programming for ‘Alarm’ output
types.
1 12 Fire Alarm, Latching Activated by alarm on Fire zone, and by user/installer ‘Bell Test’. Does not
pulse in Temporal Code 3 format. Mode and Time parameters do not
apply. [#][4][7] resets. Follows programming for ‘Alarm’ output types.
1 13 Fire Verification/Reset Normally on. Turns off on activation to reset smoke detectors. Verification
for Fire Verification Zone Function type and [System Reset] activate
output for approximately 15 sec. Mode and Time parameters do not apply.
Used for 4-wire smoke detectors.
1 14 System Trouble Activates on any System Trouble. Resets when all system troubles are
clear.
1 15 [O] Key (Trapezoid Key on RF
Key Fob)
Activates when [O] (Trapezoid key on RF Keyfob is pressed. [System
Reset] resets. Pressing [O] again also resets output when Output Mode
is set to Toggle. This output type is event-driven. See Mode (Steady,
Pulse, One Shot), Output ## on page 117 for more information.