Bosch DS7200V2-EXP Podręcznik Użytkownika Strona 126

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 156
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 125
DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 126
Bosch Security Systems | 8/04 | 4998153891C
Parity, Flow Control, Stop Bit Configuration
Address: 1255
Default: 0
Selections: 0 to 7
Parity Flow Control Stop Bits Selection
None Odd Even Software Hardware 1 2
0 X X X
1
X X X
2
X X X
3
X X X
4
X X X
5
X X X
6
X X X
7
X X X
4.8.3 DX8010 Telephone Module Configuration
DX8010 Access Options
Address: 1256
Default: 0
Selections: 0 to 15
Enter This Data Digit to Select Options
DX8010 Access Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Disabled, No DX8010 Connected
Access Granted to Users with Authority Level 1
• • • • • • • •
Access Granted to Users with Authority Level 2
Access Granted to Users with Authority Level 3
• • • • • • • •
Access Granted to Users with Authority Level 4
• • • • • • • •
Set this parameter to zero (0) if there are no DX8010 modules connected to the control panel, or to disable any
DX8010 modules that are connected to the control panel.
Selecting any of the other options allows system control for users assigned to the chosen authority level.
Przeglądanie stron 125
1 2 ... 121 122 123 124 125 126 127 128 129 130 131 ... 155 156

Komentarze do niniejszej Instrukcji

Brak uwag