DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 71
Bosch Security Systems | 8/04 | 4998153891C
4.4.5 ABC Keys and Duress Parameters
The following parameters configure the keypad’s ABC keys and the Duress function for all keypads and areas.
Each key has 16 characters of programmable text that is displayed when the key is activated (press twice to
activate).
Area Options for ABC Keys
Address:
[A] Key: 0694
[B] Key: 0696
[C] Key: 0698
Default:
DS7240V2: 15 (Areas 1 to 4)
DS7220V2: 3 (Areas 1 and 2)
Selections: 0 to 15
Enter This Data Digit to Select Options
ABC Key Area Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Disabled for all Areas
Keys work for Area 1
• • • • • • • •
Keys work for Area 2
Keys work for Area 3 (DS7240V2 only)
• • • • • • • •
Keys work for Area 4 (DS7240V2 only)
• • • • • • • •
This parameter assigns areas to the keypad ABC Keys.
Alarm Response for ABC Keys
Address:
Alarm Response for [A] Key: 0695
Alarm Response for [B] Key: 0697
Alarm Response for [C] Key: 0699
Default: 0 (No Alarm Response)
Selections:
0 = No Alarm Response
1 = Activate Fire Alarm Response
2 = Activate Panic Alarm Response
3 = Activate Emergency Alarm Response
This parameter assigns the alarm response for the ABC keys.
Fire Alarm Response: If enabled, this option displays “Fire Alarm Key #” at the text keypads. If
programmed, the control panel sends a Fire Alarm {75} report and activates the Fire Alarm output.
Panic Alarm Response: If enabled, this option displays nothing and no sounds are emitted at the keypads. If
programmed, a Panic {6} report is sent and the Burglary Alarm output is activated.
Emergency Alarm Response: If enabled, this option displays “Alarm Key #” at the text keypads. If
programmed, an Emergency Alarm {4} report is sent and the Burglary Alarm output is activated.