DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 124
Bosch Security Systems | 8/04 | 4998153891C
RF Receiver Supervision Interval
Address: 1250
Default: 5 (24 h)
Selections:
0 = No Supervision
1 = 1 h
2 = 2 h
3 = 4 h
4 = 12 h
5 = 24 h
RF transmitters (sensors) send a supervisory signal approximately once every 13 min.. The RF receiver expects to
hear this signal from every transmitter in the interval determined in this parameter. A “Missing” report is sent for
each device that the RF Receiver does not hear.
Fire transmitters have a fixed supervision interval of 4 h.
RF Jam Detect Level
Address: 1251
Default: 12
Selections: 0-15
This parameter configures the RF receivers for jam detection.
Leave the RF Jam Detect Level parameter at the default setting unless advised by Bosch Technical
Service.