DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 34
Bosch Security Systems | 8/04 | 4998153891C
Daylight Saving Clock Advance Time
• Address: 0238, 0239
• Default: 0,2 (02:00 AM)
• Selections: 0 to 22
Addresses 0238 and 0239 select the hour that the clock is advanced.
Address 0238 holds the tens digit of the hour and Address 0239 holds the ones digit of the hour. When the local
time of the control panel matches the value entered in Addresses 0238 and 0239, an hour is added to the time. To
advance the clock at midnight when the day changes from Saturday to Sunday, enter a 0 (zero) in Addresses 0238
and 0239.
Daylight Saving Clock Reverse Time
• Address: 0240, 0241
• Default: 0,3 (03:00 AM)
• Selections: 1 to 23
Addresses 0240 and 0241 select the hour that the clock is reversed.
Address 0240 holds the tens digit of the hour and Address 0241 holds the ones digit of the hour. When the local
time of the control panel matches the value entered in Addresses 0240 and 0241, an hour is subtracted from the
time.
AC Fail Report Delay
• Address: 0242, 0243
• Default: 7, 8 (120 min.)
• Selections: 0,0 to 15,15 (0 to 255 min.)
This parameter sets the number of min. (0-255) the control panel waits before sending an AC Failure report when
an AC Failure is detected. If this parameter is set to 0 (zero), there is no delay and the report is sent immediately.
If the AC Failure condition still exists at the end of the delay period, it is logged and the report is sent. If
programmed, the AC Failure output function activates when the event is logged. If AC is restored before the delay
period ends, the event is not logged and the report is not sent. If AC restoral reports are enabled, the reports are
only sent if an AC Failure report has been sent. The restoral report is sent without delay.
Addresses 0242 and 0243 must be programmed when setting the AC Fail Report Delay. The system multiplies the
entry made in Address 0242 by 16 and adds it to the entry made in Address 0243. For example, to set the AC Fail
Report Delay time to 50 min., you would enter “3” in Address 0242 (3 x 16 = 48) and then enter “2” in Address
0243 (48 + 2 = 50). Use the formula below to calculate the delay time for this parameter.
3 (Address 0242) x 16 = 48
+ 2 (Address 0243) = 50 (AC Fail Report Delay Time)
See below for commonly used time settings.
• 0,10 = 10 min. (0 x 16 = 0 + 10 = 10 min.)
• 1,14 = 30 min. (1 x 16 = 16 + 14 = 30 min.)
• 2,13 = 45 min. (2 x 16 = 32 + 13 = 45 min.)
• 3,12 = 60 min. (3 x 16 = 48 + 12 = 60 min.)
• 5,10 = 90 min. (5 x 16 = 80 + 10 = 90 min.)
• 7,8 = 120 min. (7 x 16 = 112 + 8 = 120 min.)