DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 135
Bosch Security Systems | 8/04 | 4998153891C
Network Interface Module Options
• Address: 3541
• Default: 0
• Selections: 0 to 3
Enter This Data Digit to Select Options
Network Interface Module Options 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
No Alternate Communication
•
Enable Alternate Communication
• •
Include IP Address
• •
Reserved
Reserved
• Enable Alternate Communication: Select this option to supervise the connection between the control panel
and the network interface module (DX4020). The network interface module’s DIP switch address must be set
to 134. Do not select this option if there is no network interface module connected to the system.
• Include IP Address: Select this option to use the IP address entered in IP Address 1 (2) for Destination 1 (2)
(see page 129) instead of the IP address stored in the DX4020 for network communication. Select “Enable
Alternate Communication” in Alternate Communication Options (refer to page 132) for the appropriate IP
address. Select this option when using a DX4020. Do not select this option when using a DX4010i.
4.11 DACM Configuration
The control panel supports up to 8 DACMs. However, each DACM added to the system replaces one
keypad. If 8 DACMs are added, you cannot add a keypad. For full system control, make sure at least
one text keypad is included in the system.
For complete installation, programming, addressing, and operation instructions, see the documentation
supplied with the DACM.
Configuring a DACM into the control panel is a three-step process:
1. Using Table 13 on page 80, assign the DACM’s door contact as a location. For example, DACM #1 will
be assigned to Location #5.
a. Enter “6” at Address 0726 for the device type.
b. Assign a zone function and enter it in Address 0727.
c. Assign an area to the DACM in Address 0728. Each DACM’s door contact can only use one
location.
d. Repeat the area assignment in Keypad/Door Access Control Module (DACM) Area Options. For
example, if you selected Area 1 for Address 0728, then you must enter “9” in Address 0679. This
address is for Keypad/DACM #1. “9” identifies the device as a DACM #1 in Area 1.
e. Assign a zone number in Addresses 0729-0730 if the zone number must be different than the
location number.
2. Enter the location number in DACM Location Assignment. For this example, enter “0” in Address 3546, and
“5” in Address 03547. This assigns the control panel’s Location #5 to DACM #1.
3. Assign global options in Address 3562 (see DACM Global Options on page 137). The entry you make here
affects all DACMs connected to the control panel.