DS7200V2-EXP | Expert Programming Guide | 5. Reference Materials EN | 144
Bosch Security Systems | 8/04 | 4998153891C
Table 31: Control Panel Events and Reporting Formats (continued)
Event Event as shown in
Control Panel Log
SIA Report Contact ID
Report
Event Description Zone Types
Linked to Event
RPS
Event
Group
Status
Report
115 Rstrl,Invisible
HR Holdup
Restoral
120 Panic
Restoral from alarm, Invisible zone
type.
7-Invisible Panic 8
116 Rstrl,24-hr Burg
BR Burglary
Restoral
133 24hr
(Safe)
Restoral from alarm, 24-hour
burglary zone types.
8- Burglary
15 – Door
8
117 Rstrl,Cntrl,Dly
BR Burglary
Restoral
134 Entry/Exit
Restoral from alarm, Delay 1 or 2
zone types.
11- E/E Delay 1
12- E/E Delay 2
8
118 Rstrl,Cntrl
BR Burglary
Restoral
130 Burglary
Restoral from alarm, Keyswitch,
Follower, or Instant zone types.
10- Keyswitch
13- Follower
14- Instant
8
119 Rcvr Jam
XQ RF
Interference
344 RF
Receiver Jam
Detect
Jammed condition detected on
premises RF receiver.
9 R S
120 Rcvr Jam Rstl
XH RF
Interference
Restoral
344 RF
Receiver Jam
Detect Restoral
Jammed condition detected on
premises RF receiver cleared.
9 R S
121 RF Battery Low
XT Transmitter
Battery Trouble
384 RF Low
Battery
Low Battery detected on premises
RF transmitter.
Any zone type 9
122 RF Battery Rstl
XR Transmitter
Battery Restoral
384 RF Low
Battery
Low Battery condition detected on
premises RF transmitter cleared.
Any zone type 9
123 RF Tamper Trbl
TT Tamper
Trouble
383 Sensor
Tamper
Premises RF Transmitter Tamper
Fault (Trouble).
Any zone type 9
124 RF Tamper Rstl
TR Tamper
Trouble Restore
383 Sensor
Tamper
Premises RF Transmitter Tamper
Restoral.
Any zone type 9
125 Dbus Missing
EM Expansion
Device Missing
333 Exp.
Module Failure
Data Bus device not responding to
polling.
12 R S
126 Dbus Missng,Rstl
EN Expansion
Missing Restore
333 Exp.
Module Failure
Data Bus device declared as
missing now responding to polling.
12 R S
127 Dbus Tamper
ES Expansion
Device Tamper
341 Exp.
Module Tamper
Tamper open on Data Bus Device
Tamper.
12 R S
128 Dbus Tamper,Rstl
EJ Expansion
Tamper Restore
341 Exp.
Module Tamper
Data Bus Device Tamper Restoral. 12 R S
129 Dbus Trouble
ET Expansion
Trouble
330 System
Peripheral
Trouble
Fault (Trouble) detected on Data
Bus Device.
12 R S
130 Dbus Troubl,Rstl
ER Expansion
Restoral
330 System
Peripheral
Trouble
Data Bus Device Fault (Trouble)
condition cleared.
12 R S
131 Dbus OverCurrent
YI Overcurrent
Trouble
330 System
Peripheral
Trouble
Over current condition detected on
Data Bus device.
12 R S
132 Dbus OvrCur,Rstl
YJ Overcurrent
Restore
330 System
Peripheral
Trouble
Over current condition on Data Bus
device restored.
12 R S
133 Sensor Mon Trbl NA No Activity
391 Sensor
Watch trouble
Sensor fault (trouble) detected.
Reports follow zone trouble routing.
11-15 Zone
Types
6
134 Sensor Mon Rstl
NS Activity
Restored
391 Sensor
Watch trouble
Sensor trouble condition restored.
Reports follow zone trouble routing.
11-15 Zone
Types
6
135 Sensor Reset Local Event Only
User entered System Reset key
sequence ([#][4][7]).
12