DS7200V2-EXP | Expert Programming Guide | 4. Control Panel Programming EN | 94
Bosch Security Systems | 8/04 | 4998153891C
Pulse Count
Address: See Table 17 on page 88
Default: See Table 17 on page 88
Selections:
0 = Activate on first off-normal, debounce on-board points for 160 ms
1 = Activate on first off-normal, debounce on-board points for 50 ms
2-15 = number of pulses required within the programmed Pulse Count Time for an alarm to occur
This parameter determines the number of times a sensor loop must pulse (electronically off-normal) in the Pulse
Count Time before the control panel declares the zone faulted. This applies to both on- and off-board zones.
Setting the Pulse Count to 0 (zero) tells the control panel to look for 1 pulse lasting at least 160 ms before
declaring the zone faulted.
Setting the Pulse Count to 1 tells the control panel to look for 1 pulse lasting at least 50 ms before declaring
the zone faulted.
Leave the Pulse Count parameter at the default setting (0) unless advised by Bosch Technical Service.
If a single pulse starts the Pulse Count Timer and lasts 20 sec, the control panel declares the zone
faulted regardless of the Pulse Count.
Pulse Count Time
Address: See Table 17 on page 88
Default: See Table 17 on page 88
Selections: 0-15 (see Table 21 and Table 22)
When the control panel detects a pulse (electronically off-normal), it starts a timer and waits the time selected in
this parameter to reach the Pulse Count and declare the zone faulted.
The Pulse Count Time only applies when the Pulse Count is greater than 1, or the 24-Hour Door Zone Function
Type is selected.
Use Table 21 when Location ##, Device is set to 1 (on-board zone). Use Table 22 when Location ##, Device is set to 2,
3, 4, or 5 (off-board zones).
If a single pulse starts the Pulse Count Timer and lasts 20 sec, the control panel declares the zone
faulted regardless of the Pulse Count.
Table 21: On-board Zone Pulse Count Time Selections
Pulse Count Time Selections for 50 ms
Zone Scan Time (on-board zones)
Pulse Count Time Selections for 160 ms
Zone Scan Time (on-board zones)
Selection Pulse Count Time Selection Pulse Count Time
0 0.5 sec 8 20 sec
1 1 second 9 30 sec
2 2 sec 10 40 sec
3 3 sec 11 50 sec
4 4 sec 12 60 sec
5 5 sec 13 90 sec
6 10 sec 14 120 sec
7 15 sec 15 200 sec